Vista 250FBP

Designed to integrate seamlessly with CCTV, access control and Honeywell-ADEMCO’s full range of fire and burglary components, the VISTA-250FBP provides the ultimate protection of life and property.

Category: Product ID: 2160

Honeywell-ADEMCO VISTA-250FBP

Commercial Fire and Partitioned Burglar Alarm Control Panel

SPECIFICATIONS

Electrical

  • Primary power: 18VAC @ 72VA ADEMCO No. 1451
  • Control Panel quiescent current draw: 300mA
  • Backup battery:

–       12VDC, 12AH min to 34.4AH max

–       Lead acid battery (gel type)

  • Alarm power: 12VDC, 1.7A max for each notification (bell) circuit output Total 2.3A @ 12V
  • Aux. standby pwr: 12VDC, 1A max
  • Total power: 2.3A at 12VDC, 3.4A at 24VDC from all sources
  • Standby time: 24 hours with 1A standby load using 34.4AH battery
  • Fusing: Battery input, aux. and notification (bell) circuit outputs are protected using PTC circuit protectors. All outputs are power limited.
  • Optional 24-volt power supply, PS 24 supplies two 24 VFW, 1.7A full wave rectified, unfiltered outputs

Main Dialer

  • Line seize: Double Pole
  • Ringer equiv.: 0.7B
  • Formats: ADEMCO Low Speed, ADEMCO 4+2 Express, ADEMCO High Speed, ADEMCO Contact ID,Sescoa and Radionics
  • Dual phone line capability (using 5140DLM module)

 

Cabinet Dimensions

  • 18˝ H X 14.5˝ W X 4.3˝ D

Environmental

  • Storage temp: 14° F to 158° F (-10° C to 70° C)
  • Operating temp: 32° F to 122° F (0° C to 50° C)
  • Humidity: 85% RH
  • EMI: Meets or exceeds the following requirements:

–       FCC Part 15, Class B Device

–       FCC Part 68

–       IEC EMC Directive

Agency Listings Burglary

  • UL609 Grade A Local Mercantile Premises and Mercantile Safe and Vault
  • UL611/1610 Grades A, AA, Central Station
  • UL365 Grades A, AA Police Connect

Fire

  • UL864/NFPA72 Local, Central Station and Remote Station
  • Factory Mutual
  • California State Fire Marshal
  • MEA
  • UL985

Description

Honeywell-ADEMCO VISTA-250FBP
Commercial Fire and Partitioned Burglary Alarm Control Panel

Designed to integrate seamlessly with CCTV, access control and Honeywell-ADEMCO’s full range of fire and burglary components, the new VISTA-250FBP provides the ultimate protection of life and property.

The UL listed Commercial Fire and Burglary Control Platform controls up to eight partitions, and supports up to 250 zones/points using hardwired, wireless and V-Plex addressable technologies. A diverse line of ADEMCO initiating devices, notification circuits, digital dialers, keypads, RF receivers and relays are supported by this extremely powerful control platform.

The VISTA-250FBP has been designed to mount quickly and easily in an attack resistant cabinet, and is available in 12V and 24V models. A revolutionary feature called Panel Linking allows multiple partitions, panels – even buildings – to be armed, disarmed and have status checked all from one location.

Features

  • Eight hardwired zones standard, expandable to 242 V-Plex addressable points/zones or 250 wireless points/zones
  • Can control eight separate areas independently (8 partitions)
  • Supports Panel-Linking allows up to 8 systems or building to be controlled from one central location (using VA8200)
  • Supports Commercial UL Wireless Fire and Burg
  • Stores up to 1000 events and can accommodate 250 user codes
  • Supports V-Plex addressable VistaKey access control (up to 15 doors and 500 cards)*
  • Supports up to 16 doors of access control using Vista Gateway Module (VGM)*
  • Supports CCTV applications with the new VistaView-100 CCTV Switcher Module
  • Programmable to meet SIA false alarm prevention specifications.
  • Identifies the point or zone of a fire or alarm using the new FSA- 8/FSA-24 Fire System Annunciator
  • Two on-board notification (bell) circuits delivering 2.3 amp @ 12V or 3.4 amp @ 24V
  • Automatic smoke detector sensitivity maintenance testing
  • 4-wire smoke reset using onboard J2 output trigger
  • Supports Dynamic Signaling for LRR backup
  • Supports Remote Control-via the internet**
  • Supports Internet Alarm Reporting**
  • Supports Graphical User Interface Consoles
  • Supports AlphaNumeric Pager up to eightdifferent numbers using the VA8201
  • Notification Appliance Circuits (two):
    – Programmable
    – Temporal code compliant
    – Individually silenceable
  • Programmable on-board auxiliary relay
  • SIA false alarm reduction features:
    – Exit error logic
    – Exit delay reset
    – Cross zoning
    – Call waiting defeat
    – Recent close report
  • Supports commercial hardwired, addressable polling loop and wireless zones
  • Hardwired zones
    – Provides eight style B hardwired zones
    – Supports N.O or N.C. sensors
    – Individually assignable any partition – Up to 32 two-wire smoke detectors each on zone one and two (64 total)
    – Up to 50 two-wire glassbreak detectors on zone eight
    – EOLR supervised for Fire and UL burglary installations

* Connects to Honeywell Access’ PassPoint Access Control Systems. Maximum 32 doors.
** When used with AlarmNet-i.

Additional Features

  • Patented addressable polling loop technology
    – Supports 242 two-wire zones points
    – Global polling technology for faster processing
    – Increased current draw capacity (128mA)
    – Supervised by panel
    – Individually assignable to partitions, notification circuit (bell) output or aux relay
    – 4,000 ft capability without the use of shielded cable
    – Extender/Isolation bus module
    – Two-wire smoke detector zone/group expansion module adds two or four zones
    – Eight zone – Class A and B extender module
    – Eight zone – Class B extender module
    – One zone supervised contact monitor module
  • UL Listed wireless expansion
    – Supports up to 250 wireless zones/points using 5881ENHC Receiver
    – Supervised by control for check-in signals
    – Tamper protection for transmitters
    – Individually assignable up to eight partitions
    – Supports UL864/NFPA approved wireless smoke detectors
  • Access Control Integration
    – Full integration with PassPoint Access Control System Complete Gateway interface of Vista and access functions
  • Up to 15 doors using VistaKey Access Control
  • Event reporting
  • Local printer of access or VISTA related event
  • Scheduled uploading of events to central station
  • Stored events for one call retrieval
  • Communication
    – Phone mapping by zone response type
    – Supports VIP Interactive Phone Voice Module
    – Panel operation during download
    – Uploading equipment list to central station
    – Communication to PassPoint via Vista Gateway Module
  • CCTV integration

– Supports VistaView-100 ECP based CCTV switchers

Stay Tuned!